Changzhou Pacific Electric Power Equipment Group’s 220kV power transformers feature low loss, low noise, high efficiency and strong reliability. Adopting advanced design and premium materials, they deliver excellent insulation, low partial discharge and high short‑circuit withstand strength. With stable performance, long service life and compact structure, our transformers are widely used in power grids, industrial and infrastructure projects. They ensure safe and stable operation under various working conditions, providing reliable power solutions for customers worldwide.
Introduction to 220kV (Um=252kV) Power Transformer
Our company's 220kV power transformer (with system maximum voltage Um=252kV) is suitable for 220kV high-voltage transmission networks. The product is more strictly designed in terms of insulation, mechanical strength and process control to achieve low partial discharge, high short-circuit resistance and long-term maintenance-free goals. The core and structural components are optimized and rounded in terms of electric field. The coils use staggered conductors and undergo strict wave processes and mechanical force analyses. The insulation and cooling structures are specially designed. The body is made of high-strength laminated products with pressure plates and supports. The oil tank adopts a full vacuum design, with advanced sealing and oil injection processes, and the equivalent air-drying time is controlled. The entire production process of the product is carried out in a dust-proof environment, and the quality system is complete.
Product Parameters
| Rated Capacity (kVA) | Voltage Combination | Connection Group Symbol | No-load Loss (kW) | Load Loss (kW) (75℃) | No-load Current (%) | Short-circuit Impedance (%) | ||
| High Voltage (kV) | High Voltage (kV)% |
Low Voltage kV |
22 | |||||
| 3150 |
35~ 38.5 |
±2x2.5% 土5% |
3.15 6.3 10.5 |
Yd11 |
1.7 | 20.7 | 0.45 | 7.0 |
| 4000 | 2.0 | 24.6 | 0.45 | |||||
| 5000 | 2.4 | 28.2 | 0.35 | |||||
| 6300 | 2.9 | 31.5 | 0.35 | 8.0 | ||||
| 8000 | ±2x2.5% |
3.15 3.3 6.3 6.6 10.5 |
YNd11 | 4.0 | 34.6 | 0.30 | ||
| 10000 | 4.8 | 40.8 | 0.30 | |||||
| 12500 | 5.5 | 48.4 | 0.30 | |||||
| 16000 | 6.7 | 59.2 | 0.25 | |||||
| 20000 | 7.9 | 71.6 | 0.25 | |||||
| 25000 | 9.4 | 84.6 | 0.28 | 10.0 | ||||
| 31500 | 11.1 | 100.8 | 0.28 | |||||
|
Rated Capacity kV-A |
Voltage Combination | Connection Group Symbol | No-load Loss (kW) | Load Loss (kW) | No-load Current (%) | Short-circuit Impedance (%) | |
| High Voltage and Tap Range (kV) | Low Voltage | 22 | |||||
| 6300 |
110±2x2.5% 115±2x2.5% 121±2x2.5% |
6.3 6.6 10.5 |
YNd11 | 4.1 | 32.0 | 0.62 | 10.5 |
| 8000 | 4.9 | 38.0 | 0.62 | ||||
| 10000 | 5.8 | 45.0 | 0.58 | ||||
| 12500 | 6.8 | 53.0 | 0.58 | ||||
| 16000 | 8.3 | 65.7 | 0.54 | ||||
| 20000 | 9.7 | 79.0 | 0.54 | ||||
| 25000 | 11.4 | 94.0 | 0.50 | ||||
| 31500 | 13.5 | 111 | 0.48 | ||||
| 40000 | 16.2 | 133 | 0.45 | ||||
| 50000 | 19.4 | 158 | 0.42 | ||||
| 63000 | 22.9 | 187 | 0.38 | ||||
| 75000 |
13.8 15.75 18 21 |
26.0 | 212 | 0.33 | 12~14 | ||
| 90000 | 29.9 | 245 | 0.30 | ||||
| 120000 | 37.3 | 303 | 0.27 | ||||
| 150000 | 44.1 | 359 | 0.24 | ||||
| 180000 | 49.5 | 411 | 0.20 | ||||
|
Note 1: For step-up transformers, a tapless structure is recommended. Taps can be provided if required by operation. Note 2: When the annual average load factor of the transformer is between 42% and 46%, the maximum operating efficiency can be achieved using the loss values in the table. | |||||||
|
Rated Capacity kV-A |
Voltage Combination | Connection Group Symbol | No-load Loss (kW) | Load Loss (kW) | No-load Current (%) | Short-circuit Impedance (%) | |
| High Voltage and Tap Range (kV) | Low Voltage | 22 | |||||
| 31500 |
220±2×2.5% 242±2×2.5% |
6.3 6.6 10.5 |
YNd11 | 15 | 115 | 0.56 | 12~14 |
| 40000 | 18 | 134 | 0.56 | ||||
| 50000 | 21 | 161 | 0.52 | ||||
| 63000 | 25 | 188 | 0.52 | ||||
| 75000 |
10.5 13.8 |
29 | 213 | 0.48 | |||
| 90000 | 34 | 246 | 0.44 | ||||
| 120000 | 41 | 304 | 0.44 | ||||
| 150000 |
10.5、13.8 11、13.8 15.75 18、20 |
49 | 360 | 0.40 | |||
| 160000 | 51 | 378 | 0.39 | ||||
| 180000 | 56 | 413 | 0.36 | ||||
| 240000 | 70 | 484 | 0.33 | ||||
| 300000 |
15.75 18 20 |
83 | 577 | 0.30 | |||
| 360000 | 95 | 662 | 0.30 | ||||
| 370000 | 97 | 675 | 0.30 | ||||
| 400000 | 103 | 716 | 0.28 | ||||
| 420000 | 106 | 742 | 0.28 | ||||
| Note 1: Transformers with a rated capacity of less than 31500 kVA and those with other voltage combinations can also be provided upon request.Note 2: Transformers with a low voltage of 35 kV and 38.5 kV can also be provided upon request. | |||||||
Product Introduction
Transformer Features
Our company manufactures transformers with the following characteristics: low loss, low noise, low partial discharge, no leakage, and strong short-circuit resistance. They do not require core lifting during on-site installation, and the transformer body is maintenance-free for 20 years. Below are the main features of transformers with voltage ratings below 110 kV in terms of structure and process.
Core Section
1.Core Material and Structure
High-performance grain-oriented silicon steel sheets are selected for the core. The core adopts a fully oblique multi-stage step joint structure, and the non-overlapping yoke process is used, which helps reduce no-load losses and noise.
2.Core Assembly
The core column and yoke are bound using high-strength resin mesh banding materials, mechanically bundled and cured. This ensures good core perpendicularity.
3.Mechanical Strength
The core structure has high mechanical strength. Notably, the frame structure made of large laminated clamp plates effectively clamps the core together, ensuring sufficient short-circuit mechanical strength. This design also meets the requirement for no core lifting during transportation and on-site installation.
4.Core Connectors
All core structural components are rounded to avoid sharp edges. In areas with high field strength where lead wires pass through, special insulation sheaths are added to reduce partial discharge.
5.Electrical Reliability
All core component connections are left unpainted to ensure reliable electrical connection and prevent localized electrical potential. Both the clamps and core are grounded separately.
Coil Section
1.Electrical Structure Design
Electrical structural parameters are calculated using analysis software.
2.Voltage Distribution
All coils are analyzed using wave process calculation software for voltage distribution and repeatedly adjusted to ensure a reasonable gradient distribution. The electrical field strength of the transformer body is also verified to ensure optimal main longitudinal insulation parameters and electrical strength.
3.Coil Insulation
All coils are wound on hard insulation tubes that have been pre-dried and impregnated with oil for pre-stabilization. The outer coils are supported with external support strips, and additional auxiliary support strips are added inside the inner coils to improve short-circuit resistance.
4.Short-Circuit Resistance
Based on short-circuit mechanical force calculations, self-adhesive transposed conductors or semi-rigid conductors are used for the inner coils, which have extremely high mechanical strength and meet short-circuit resistance requirements.
5.Enhanced Short-Circuit Strength
All coil terminals and end parts are bound with high-shrink polyester heat-shrink tubes and heat-shrink tapes to increase short-circuit resistance.
6.Coil Structure and Cooling
The inner and outer coil spacers are designed based on calculated values and may differ, ensuring a rational distribution. The coils are equipped with a guided cooling structure for optimal heat dissipation. In addition, heat-pressed insulation molded parts replace traditional cardboard spacer strips at the coil transposition points. The oil gap spacer blocks are rounded and pre-impregnated, improving axial short-circuit resistance.
7.Vacuum Drying and Assembly
After vacuum drying, individual coils are assembled in phase. The main oil gap spacers between the coils are fixed using special positioning plates. After vacuum drying the coils, their heights are checked and adjusted to ensure that coils in the same phase are under consistent load, improving short-circuit strength.
Transformer Body Section
1.Body Structure
The transformer body adopts a single-phase structure. The body press plates are made of laminated insulation board or laminated wood, which have sufficient short-circuit impact resistance.
2.Compression Structure
The compression structure of the body uses laminated insulation board press blocks instead of traditional nails, increasing the cross-sectional area of the compression blocks and reducing the compression force. This structure uses hydraulic devices to set a pre-compression force during assembly after the drying process.
3.Lead Supports
All lead supports are made of high-density laminated wood and form a frame structure. Some lead supports are formed using laminated insulation paperboard, which increases both mechanical and electrical strength. All supports use laminated wood insulation nuts with a special anti-loosening structure.
Oil Tank and Assembly Section
1.Vacuum Oil Tank
All transformers rated for 110 kV and below use a fully vacuum-sealed oil tank with a barrel-shaped structure. The upper and lower sections of the oil tank can be connected either by bolts or welded to meet the requirement for no core lifting and maintenance-free operation. The inside of the oil tank is fully polished and rounded.
2.Oil Conservator
All transformer oil conservators can withstand full vacuum strength and are equipped with airbags and pointer-type oil level indicators. After all transformer accessories are assembled, the conservator can be evacuated to a full vacuum before oil injection, effectively preventing the formation of bubbles inside the insulation components and transformer, reducing partial discharge.
3.Sealing Structure
The sealing surfaces of the transformer, including bushings, adopt a hard connection structure with limit grooves, and high-quality sealing components are used with sealing adhesives to ensure no leakage.
4.Positioning and Reliability
The transformer is equipped with a special upper and lower positioning structure, which ensures reliability, resistance to transportation shocks, and meets the requirement for no core lifting during installation.
5.Secondary Wiring
Secondary wiring is arranged according to the user’s requirements, using stainless steel cable trays or armored cables, and all wiring is connected to terminal boxes to facilitate user installation.
6.Advanced Assembly Process
The transformer body undergoes an equivalent exposure time control from drying to vacuum oil impregnation, ensuring continuous high-vacuum degassing during the assembly of all accessories. This effectively controls moisture absorption in insulation components.
Quality Control
Our company’s entire transformer production process follows an advanced process management system for quality control. Processes such as wire production, insulation material fabrication, coil manufacturing, and body assembly are all carried out in dust-free work zones, with the air cleanliness controlled to 3 μg/cm²·day or below.
Company Profile
Changzhou Pacific Electric Equipment (Group) Co., Ltd. Is one of the few high-tech enterprises in China that possess the comprehensive integration capabilities for the entire high and low voltage power transmission and distribution industry chain. Since its establishment in 1989 and the implementation of group operation in 1997, the company has a registered capital of 130 million yuan and has formed an integrated industrial layout covering research and development, manufacturing, and services.
The company has a comprehensive industrial park covering an area of 240,000 square meters, with a construction area of 120,000 square meters and fixed assets of 500 million yuan. It produces over 20,000 sets of various electrical equipment annually, and has a complete industrial chain supporting capacity.
Our core strength lies in the integration and service of the entire value chain:
Industry resource integrator: Served as a standing director of the China Electrical Appliance Industry Association and held leadership positions in several specialized branches, integrating industry resources and promoting the coordinated development of the industrial chain.
The most comprehensive product range: We offer a complete product line covering high-voltage switchgear, power transformers, ring-main units, low-voltage intelligent distribution, and integrated substations, and possess the unique ability to provide customers with a one-stop power transmission and distribution solution.
Innovation throughout the industrial chain: As a national-level high-tech enterprise, the R&D covers all stages from components to system integration, emphasizing technical collaboration and system optimization among products, and enhancing the advancement and economy of the overall solution.
Full-chain quality control: Establish a quality management system covering the entire industrial chain, implementing standardized operations and clean production from raw materials to final assembly. Through comprehensive testing methods, ensure consistent quality at all stages of the industrial chain.
Integrated and verified solution: Leveraging the advantages of a complete industrial chain, the company's solutions have been successfully applied to power grid construction, urban development, industrial upgrading, and new energy projects, demonstrating excellent system compatibility and overall efficiency.
Customer-oriented industrial chain services: Adhering to the concepts of "professionalism, integrity, cooperation, and innovation", we provide a full industrial chain service ranging from consultation and design, product selection, installation and commissioning to operation and maintenance support. We are committed to reducing the overall costs for customers through resource integration and enhancing investment value.
Relying on a complete industrial chain layout and one-stop service capabilities, the company can quickly respond to the diverse needs of customers and become an efficient partner for power engineering projects.